MDC-714i Modbus Data Concentrator (1x Ethernet+ 1 x RS-232, 1 x RS-485, 3x isolated RS485)

£343.00
£343.00
(-0%)
(Price excludes VAT)
Modbus Data Concentrator (1x RS232 + 1x non-isolated and 3x isolated RS485 ports). Access ModbusRTU slaves from Mulitple ModbusTCP Masters. Increases efficiency and read-times.
Model: MDC-714i
Subtotal: £343.00

Free Shipping Free standard shipping on orders over £500

Free Returns 30 Day Money Back Guarantee
icon

UK company

icon

40 years experience

icon

Talk to our expert engineers

MDC-714i  Modbus Data Concentrator (1x Ethernet+ 1 x RS-232, 1 x RS-485, 3x isolated RS485)

MDC-714i Modbus Data Concentrator (1x Ethernet+ 1 x RS-232, 1 x RS-485, 3x isolated RS485)

£343.00

MDC-714i Modbus Data Concentrator (1x Ethernet+ 1 x RS-232, 1 x RS-485, 3x isolated RS485)

£343.00

The MDC-700 series is a Modbus Data Concentrator used to access data from disparate Modbus slave devices with a contiguous Modbus address table ranged by the concentrator. Up to 240 Modbus/RTU commands can be performed to read data from Modbus slave devices via RS-232/485, and up to 8 Modbus/TCP masters are allowed to get the polled data via the Ethernet. The Modbus/TCP masters directly read/write the data in the MDC-700 instead of polling each Modbus/RTU slave device one by one. This way not only makes the data on the RS-232/485 sharable to multiple Modbus/TCP master but also shorten the time to read/write data from/to multiple Modbus/RTU slave devices.

Editing the Modbus/RTU commands for accessing the Modbus RTU slaves is simple and convenient with Comma Separated Values (CSV) format. In addition, a web-based user interface is provided to configure the concentrator and remotely monitor the state of the connection of Modbus RTU slaves.

MDC700 Application

  • Web-based user interface
  • Easy configuration with .CSV file
  • Supports the Modbus RTU master and slave
  • Support for up to 8 Modbus TCP masters
  • Data pool for up to 9600 registers
  • Modbus polling commands for up to 240 definitions
  • Upgrade Modbus/RTU devices with Ethernet communication ability
  • Speed up the time for reading from multiple Modbus/RTU devices
Display
Type 5 x Digit 7 Segment LED Display
LED Indicators
Status 1 x System, to display heart beat
Ethernet
Ports x1, 10/100 Base-TX
Protocol Modbus/TCP Slave
COM Ports
Ports 1 x 5-wire RS-232, 1 x 2-wire RS-485, 3 x 2-wire RS-485 (2500 VDC Signal Isolation)
Baud Rate 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
Data Format N81, E81, O81
Protocol Modbus RTU Master/Modbus RTU Slave
Polling Definition 250 definitions for all RS-232/485 ports
Shared Memory 9600 registers for each of AI, AO, DI and DO data
Power
Input Range +10 VDC ~ +30 VDC (non-regulated)
Consumption 2.5 W
Mechanical
Casing Metal
Dimensions (mm) 102 mm x 125 mm x 28 mm (W x H x D)
Installation Wall Mounting
Environment
Operating Temperature -25 ~ +75 °C
Storage Temperature -30 ~ +80 °C
Humidity 10 ~ 90% RH, non-condensing

 