DNP-211-S DNP3 Slave to Modbus TCP Client Gateway

DNP-211-S DNP3 Slave to Modbus TCP Client Gateway

£580.00
£580.00
(-0%)
(Price excludes VAT)
DNP3 Slave to ModbusTCP Client gateway
Model: DNP-211-S
Subtotal: £580.00

Free Shipping Free standard shipping on orders over £500

Free Returns 30 Day Money Back Guarantee
icon

UK company

icon

40 years experience

icon

Talk to our expert engineers

DNP-211-S DNP3 Slave to Modbus TCP Client Gateway

DNP-211-S DNP3 Slave to Modbus TCP Client Gateway

£580.00

DNP-211-S DNP3 Slave to Modbus TCP Client Gateway

£580.00

Distributed Network Protocol 3 (DNP3) is a set of communications protocols used between components in process automation systems. Its main use is in utilities such as electric and water companies. It was developed for communications between various types of data acquisition and control equipment. It plays a crucial role in SCADA systems. It is primarily used for communications between a master station and Remote Terminal Units (RTUs) or Intelligent Electronic Devices (IEDs). 

The DNP-211-S is a gateway device that supports the conversion between DNP3 Outstation and Modbus TCP Master protocols. It integrates multiple Modbus TCP I/O devices into a single DNP3 I/O device, allowing the DNP3 master station in the system to control the underlying Modbus TCP I/O devices through the DNP-211-S. On the Modbus side, the DNP-211-S supports common function codes such as 1, 2, 3, 4, 5, 6, 15, and 16. On the DNP3 side, it provides corresponding data groups such as 1, 10, 11, 30, 40, and 41. All Modbus TCP I/O data and DNP3 address mappings can be configured through the DNP-211-S utility software.

  • Integrate Modbus TCP slaves and convert to a DNP3 slave
  • DNP3 supports connections via RS-485, TCP/IP, and UDP
  • Configurable mapping data points
  • DNP3 supports Binary, Binary Output, Analog, and Analog Output data
  • Analog and Analog Output data support word, int32, float, and double formats
  • Modbus TCP supports function code 1, 2, 3, 4, 5, 6, 15, 16
  • DNP3 data provides the Modbus TCP connection status
  • Supports up to 32 Modbus TCP slaves
Software
OS Linux Kernel 3.2.14
Protocol DNP3 slave:
• Data Group:1, 10, 11, 30, 40, 41
• Connection: RS-485 / TCP / UDP
• Data Points:
DI: 8192
DO: 8192
AI: 2048
AO: 2048

Modbus TCP client:
• Function:1, 2, 3, 4 , 15, 16
• Connection: Max. 32 Modbus TCP servers
Service SFTP server
Main Unit
CPU Cortex-A8, 1 GHz
System Memory 512 MB DDR3 SDRAM
Real Time Clock Yes (Provide seconds, minutes, hours, day of week, month, year)
Watchdog Timer Yes, Dual Watchdog Timer
Display
Signal VGA (Analog RGB)
LED Indicators
Status 1 x PWR(Power)
1 x RUN(Running)
1 x L1
1 x L2
1 x L3
Ethernet
Ports 2 x RJ-45, 10/100/1000 Base-TX
COM Ports
Ports 1 x RS-232 (Console, Non-isolated)
1 x RS-232, Non-isolated
1 x RS-485, Non-isolated
1 x RS-485 (2500 VDC, Isolated)
USB
Ports 2
Specification USB 2.0 (Host)
Power
Input Range +12 VDC ~ +48 VDC
Consumption 4.8 W
Mechanical
Casing Metal
Dimensions (mm) 35 x 167 x 119 (W x L x H)
Installation DIN-Rail or Wall Mounting (optional)
Environment
Operating Temperature -25 ~ +75 °C
Storage Temperature -40 ~ +80 °C
Humidity 10 ~ 90% RH, Non-condensing

 

Related Products

Recently Viewed Products