ADPT-LP0xX Differential Air Pressure Transmitter w/LCD

ADPT-LPF0xX Differential Air Pressure Transmitter w/LCD

£143.00
£143.00
(-0%)
(Price excludes VAT)
Differential Air Pressure Transmitter/Sensor for monitoring positive, negative or differential pressures of up to 2000pa/20mbar. With , 0-5V, 0-10Vdc or 4-20mA signal output. Ranges available from 0-100 to 0-2000 pa. LCD Display. +/- 1% F.S.O. Accuracy
Model: ADPT-LPF00X
Subtotal: £143.00

Free Shipping Free standard shipping on orders over £500

Free Returns 30 Day Money Back Guarantee
icon

UK company

icon

40 years experience

icon

Talk to our expert engineers

ADPT-LP0xX Differential Air Pressure Transmitter w/LCD

ADPT-LPF0xX Differential Air Pressure Transmitter w/LCD

£143.00

ADPT-LPF0xX Differential Air Pressure Transmitter w/LCD

£143.00
Pressure Range: 00: ±4" ±2" ±1"; 0 - 4" 0 - 2" and 0 - 1" WC
Static Probe: No

The LP series is used to measure positive, negative or differential pressure. The piezoresistive sensor is ideal for monitoring the pressure of air or other clean inert gas. Typical HVAC applications include monitoring of filter differential pressure or VAV applications. An integrated static pressure probe provides ease of installation for duct mounting. Several accessories are available. A weatherproof polycarbonate enclosure is provided for electrical connections and ease of installation.

The ADPT-LP0xX includes a LCD Display for pressure readout. 
NOTE: Please choose range and if static probe is required, just above the Add to Cart button.

  • Jumper selectable 2 wire current (4-20mA) and 3 wire voltage outputs (0-5V or 0-10V)
  • 24 Vac/dc power supply
  • Six variable jumper selectable pressure ranges, W.C.
  • Hinged Polycarbonate weatherproof enclosure
Models Pressure Ranges
00 ±1”, ±2”, ±4”, 0-1”,  0-2”, 0-4” W.C.  
01 ±3“, ±5”, ±8“, 0-3” , 0-5”, 0-8”W.C. 
02 ±6“, ±10”, ±12“, 0-6” , 0-10”, 0-12”W.C.
03 ±10“, ±15”, ±20“, 0-10” , 0-15”, 0-20”W.C.
04 ±250, ±500, ±1000, 0-250, 0-500, 0-1000 Pa
05 ±500, ±1000, ±2000, 0-500, 0-1000, 0-2000 Pa

 

  • Accuracy: ±1% F.S.O.
  • Measurement Type: Differential (two port), Static,  Velocity, & Total Pressure
  • Response Time: 250 ms
  • Stability: < ±1% F.S.O. per year
  • Thermal Effects: < ±3% over compensated range
  • Compensated Range: 0 - 50Ëš C (32 - 122ËšF)
  • Proof Pressure: 40”  W.C. (100“ for 10” & 20“ Models)
  • Burst Pressure: 60”  W.C. (200“ for 10” & 20“ Models)
  • Operating Conditions: 0 - 70ËšC (32 - 158ËšF),  10 - 90 %RH, non condensing
  • Power Supply: 20 - 28 Vac/dc   (non-isolated half-wave rectified)
  • Supply Current: < 4 mA
  • Input Voltage Effect: Negligible over operating range
  • Protection Circuitry: Reverse voltage protected and output limited
  • Output Signal: 4-20 mA (2-wire), 0-5 or   0-10 Vdc (3-wire), switch selectable
  • Output Drive Capabilities:
    Current: 400 ohms max @ 24 vdc 
    Voltage: 10K ohms min
  • Zero Adjustments: Pushbutton auto-zero
  • Wiring Connections: Screw terminal block (14 to 22 AWG)
  • Pressure Connection: Barbed ports for 5 mm  (0.170“ ID) flexible tubing
  • Conduit Connection: ½” NPT conduit or cable gland
  • Display: 3½ digit LCD, 0.4“ digit height
  • Enclosures: Polycarbonate UL94-V0, IP65 (NEMA 4X)
  • Approvals:  CE, RoHS
  • Country of Origin: Canada
  • HVAC (Heating, Ventillation and Air Conditioning) systems / VAV (Variable Air Volume) systems
  • Process Control
  • Air Flow Monitoring
  • Drop Across Air Filters
  • Hydraulic Pressures
  • Pneumatic Pressures