CL-213-E  PM2.5, CO, CO2, Temp, RH, Dew point Data Logger (Enet)

CL-213-E PM2.5, CO, CO2, Temp, RH, Dew point Data Logger (Enet)

£519.00
£519.00
(-0%)
(Price excludes VAT)
PM2.5, CO + CO2, Temperature and Relative Humidity Data Logger. RS485 communications. Standalone or use as part of a monitoring solution. Modbus RTU/TCP & MQTT Protocols supported.
Model: CL-213-E
Subtotal: £519.00

Free Shipping Free standard shipping on orders over £500

Free Returns 30 Day Money Back Guarantee
icon

UK company

icon

40 years experience

icon

Talk to our expert engineers

CL-213-E  PM2.5, CO, CO2, Temp, RH, Dew point Data Logger (Enet)

CL-213-E PM2.5, CO, CO2, Temp, RH, Dew point Data Logger (Enet)

£519.00

CL-213-E PM2.5, CO, CO2, Temp, RH, Dew point Data Logger (Enet)

£519.00

The CL-200 series of data logger devices can be used to record PM2.5, CO, CO2, temperature, humidity and dew point information, including the date and time stamps, and are able to store up to 450,000 downloadable records.


Real-time data can be accessed from the CL-200 data logger from anywhere and at any time using the free Windows software, the iOS App, or the Android App, as long as they are connected to the same local network as the data logger.


Support is provided for common industrial protocols such as DCON, Modbus RTU, and Modbus TCP, as well as the emerging machineto- machine (M2M)/)IoT (Internet of Things) connectivity protocol – MQTT. The CL-200 data logger can be connected via widely used communication interfaces including RS-485, Ethernet and PoE, meaning that the device can be easily integrated into existing HMI or SCADA systems, ensuring trouble-free maintenance in distributed control systems.


 

Supports the MQTT Protocol for IoT Applications Multi-platform Remote Access Software
CL-200 MQTT Real-time data from the CL-200 data logger can be accessed from anywhere and at any time using the DL300 Utility, the iOS or Android App, or via a regular web browser, as long as they are connected to the same local network as the data logger.
CL-200 Remote Access

 

 

  • Able to record PM2.5, CO, CO2, Temperature, Humidity and Dew Point Measurements
  • Non-dispersive Infrared (NDIR) CO2 Sensor (CL-212/3-E)
  • Up to 450,000 records with date and time stamps
  • Supports the DCON, Modubs RTU/TCP, and MQTT Protocols
  • Includes RS-485/Ethernet Communication Interfaces
  • Relay Output for Alarm or IAQ Device Control

System Specifications

Model CL-211-E CL-212-E CL-213-E
System
PM2.5/CO/CO2/RH/T Alarm Yes
Real Time Clock Yes
Data Logger Yes, up to 450,000 records
Relay Output Form A×1, SPST
30 VDC @ 16 A or 250 VAC @ 16 A
Interface RS-485/Ethernet
Electrical
Powered from Terminal Block +12 to +48 VDC
Power Consumption Non-PoE 2.66 W (Max.) 2.9 W (Max.) 3.24 W (Max.)
PoE 2.73 W (Max.) 3.22 W (Max.) 3.41 W (Max.)
Mechanical
Installation Ceiling Mounting/Wall Mounting
Protection Class IP20
Dimensions (D x H) Ø 150 mm x 53 mm
Environment
Operating Temperature 0 to +50°C
Storage Temperature -30 to +75°C
Humidity 10 to 90% RH, Non-condensing

I/O Specifications

 

Model CL-211-E CL-212-E CL-213-E
PM2.5 Measurement
Range 0 ~ 400 μg/m3
Resolution 1μg/m3
Response Time <= 1 min.
CO Measurement
Range 0 to 1000 ppm (Electrochemical) - 0 to 1000 ppm
(Electrochemical)
Resolution 1 ppm - 1 ppm
Accuracy ±5% of measured value - ±5% of measured value
Response Time 30 seconds - 30 seconds
Warm-up Time 300 seconds - 300 seconds
CO2 Measurement
Range - 0 to 9999 ppm (NDIR)
Resolution - 1 ppm
Accuracy - ±40 ppm ±3% of measured value
Response Time - 120 seconds
Warm-up Time - 5 minutes
Temperature Measurement
Range -10 to +50°C
Resolution 0.1°C
Accuracy ±0.6°C
Relative Humidity Measurement
Range 0 to 100% RH
Resolution 0.1% RH
Accuracy ±5% RH
Dew Point
Range Calculated using temperature and relative humidity
Resolution 0.1°C
 

 

Related Products